Flame arresters designed to prevent the transmission of a deflagration fitted with two pipe connections one on each side of the flame arrester element. They are static flame arrester measurable type to be thereby charcterised by that the quenching gaps of the flame arrester element can be technically drawn, measured and controlled. It can be designed bidirectional which prevents T flame transmission from both sides. The integrated temperature sensor integrated by the manufacturer used to indicate a stabilized flame into the flame arrester.

Pipe Protection
Design Protection System
Tube protection against deflagration
Tube protection against detonation
Protection against continuous fire
Approval EC type examination certificate based on to directive 94/9/EC, according to ATEX 95 and ISO 16852
Protection Gas/air or steam/air mixtures of the following explosion groups:
– I (methane) NSW ≥ 1.14 mm
– IIA (D) NSW ≥ 0.90 mm
Pipe Sizes 1⁄2″, 3⁄4″, 1″, 11⁄4″
Connection Standards Rp according to ISO 71 (DIN 2999)
BSP according to BS 21
NPTF according to ANSI B1.20.3
Materials Strip protection: Stainless Steel
Body/cap: Stainless Steel, Carbon Steel
Coating Optional
Pipe Protection
Protection System Tube protection against deflagration
Tube protection against detonation
Protection against continuous fire
Approval EC type examination certificate based on directive 94/9/EC, according to ATEX 95 and ISO 16852
Protection Gas/air or steam/air mixtures of the following explosion groups:
– I (methane) NSW ≥ 1.14 mm
– IIA (D) NSW ≥ 0.90 mm
Pipe Sizes DN15, DN20, DN25, DN32
1/2″, 3/4″, 1″, 11⁄4″
Connection Standards DIN 2501 PN10
ANSI B16.5 – 150 RF
Materials Strip protection: Stainless Steel
Body/cap: Carbon Steel, Stainless Steel
Coating Optional
Pipe Protection
Protection System Tube protection against deflagration
Tube protection against detonation
Approval EC type examination certificate based on directive 94/9/EC, according to ATEX 95 and ISO 16852
Protection Gas/air or steam/air mixtures of the following explosion groups:
– I (methane) NSW ≥ 1.14 mm
– IIA (D) NSW ≥ 0.90 mm
– IIB3 (C) NSW ≥ 0.65 mm
– IIC (B) NSW ≥ 0.50 mm
Pipe Sizes 1/8″, 1/4″, 3/8″, 1/2″
Connection Standards Rp according to ISO 71 (DIN 2999)
BSP according to BS 21
NPTF according to ANSI B1.20.3
Materials Strip protection: Stainless Steel, Special Alloys
Body/cap: Stainless Steel, Special Alloys
Pipe Protection
Protection System Tube protection against deflagration
Approval EC type examination certificate based on directive 94/9/EC, according to ATEX 95 and ISO 16852
Protection Gas/air or steam/air mixtures of the following explosion groups:
– I (methane) NSW ≥ 1.14 mm
– IIA (D) NSW ≥ 0.90 mm
Pipe Size 11/2“
Connection Standards Rp according to ISO 71 (DIN 2999)
BSP according to BS 21
NPTF according to ANSI B1.20.3
Materials Strip protection: Stainless Steel
Body/cap: Carbon Steel, Stainless Steel
Coating Optional
Temperature Sensor Resistance thermometer with ignition protection type
– Inherently safe (E Ex i)
– Pressureresistant enclosure (E Ex d)
Pipe Protection
Protection System Tube protection against deflagration
Approval EC typeexamination certificate based on directive 94/9/EC, according to ATEX 95 and ISO 16852
Protection Gas/air or steam/air mixtures of the explosion groups:
– I (methane) NSW ≥ 1.14 mm
– IIA (D) NSW ≥ 0.90 mm
Pipe Sizes DN40
11/2“
Connection Standards DIN 2501 PN10
ANSI B16.5 – 150 RF
Materials Strip protection: Stainless Steel
Body/cap: Carbon Steel, Stainless Steel
Coating Optional
Temperature Sensor Resistance thermometer with ignition protection type
– Inherently safe (E Ex i)
– Pressureresistant enclosure (E Ex d)
Pipe Protection
Protection System Tube protection against deflagrationbr
Tube protection against detonation
Approval EC type examination certificate based upon Directive 94/9/EC, according to ATEX 95 and ISO 16852
Protection Gas/air or steam/air mixtures of the explosion groups:
– I (methane) NSW ≥ 1.14 mm
– IIA (D) NSW ≥ 0.90 mm
– IIB3 (C) NSW ≥ 0.65 mm
– IIC (B) NSW ≥ 0.50 mm
Pipe Sizes DN25, DN32, DN40, DN50, DN65, DN80
1″, 11⁄4″, 11⁄2″, 2″, 21⁄2″, 3″
Connection Standards DIN 2501 PN10
ANSI B16.5 – 150 RF
Materials Strip protection: Stainless Steel, Special Alloys
Rust cage: Stainless Steel, Special Alloys
Body: Carbon Steel, Stainless Steel, Special Alloys
Coating Optional
Temperature Sensor Resistance thermometer with ignition protection type
Inherently safe (E Ex i)
Pressureresistant enclosure (E Ex d)
Pipe Protection
Protection System Tube protection against deflagration
Tube protection against detonation
Approval EC type examination certificate based upon Directive 94/9/EC, according to ATEX 95 and ISO 16852
Protection Gas/air or steam/air mixtures of the explosion groups:
– I (methane) NSW ≥ 1.14 mm
– IIA (D) NSW ≥ 0.90 mm
– IIB3 (C) NSW ≥ 0.65 mm
– IIC (B) NSW ≥ 0.50 mm
Pipe Sizes 1″, 11⁄4″, 11⁄2″, 2″, 21⁄2″, 3″
Connection Standards Rp according to ISO 71 (DIN 2999)
BSP according to BS 21
NPTF according to ANSI B1.20.3
Materials Strip protection: Stainless Steel, Special Alloys
Rust cage: Stainless Steel, Special Alloys
Body: Carbon Steel, Stainless Steel, Special Alloys
Coating Optional
Temperature Sensor Resistance thermometer with ignition protection type
– Inherently safe (E Ex i)
– Pressureresistant enclosure (E Ex d)
Pipe Protection
Protection System Tube protection against deflagration
Tube protection against detonation
Approval EC type examination certificate based upon Directive 94/9/EC, according to ATEX 95 and ISO 16852
Protection Gas/air or steam/air mixtures of the explosion groups:
– I (methane) NSW ≥ 1.14 mm
– IIA (D) NSW ≥ 0.90 mm
– IIB3 (C) NSW ≥ 0.65 mm
– IIC (B) NSW ≥ 0.50 mm
Pipe Sizes 1″, 11⁄4″, 11⁄2″, 2″, 21⁄2″, 3″
Connection Standards Rp according to ISO 71 (DIN 2999)
BSP according to BS 21
NPTF according to ANSI B1.20.3
Materials Strip protection: Stainless Steel, Special Alloys
Rust cage: Stainless Steel, Special Alloys
Body: Carbon Steel, Stainless Steel, Special Alloys
Coating Optional
Temperature Sensor Resistance thermometer with ignition protection type
– Inherently safe (E Ex i)
– Pressureresistant enclosure (E Ex d)